All Steel
|
| All Steel |
Benefits |

|
- Lightweight for ease of handling
- Excellent ultimate load performance
- Painted finish for lifetime protection
- Interchangeable with other panel strengths
- Completely non-combustible
- Excellent grounding and electrical continuity
- Flame spread and smoke development rating: Class A
|
| Related Applications >> Data Centers : Renovations |
| All Steel
Performance Specifications |
| System Type
|
System Weight
|
Static Loads
|
Rolling Loads
|
Impact Loads |
| Panel |
Understructure |
|
Concentrated
Loads |
Uniform Loads |
Ultimate Loads* |
10
Passes |
10,000
Passes |
|
| All Steel 1000 |
Bolted Stringer |
6.0 lbs/ft²
30 kg/m²
|
1000 lbs
454 kg |
250 lbs
113 kg |
Min 2.5 |
400 lbs
181 kg |
400 lbs
181 kg |
150 lbs
68 kg |
| All Steel 1250 |
Bolted Stringer |
7.0 lbs/ft²
35 kg/m²
|
1250 lbs
567 kg |
300 lbs
136 kg |
Min 2.5 |
500 lbs
227 kg |
500 lbs
227 kg |
150 lbs
68 kg |
| All Steel 1500 |
Bolted Stringer |
8.5 lbs/ft²
41 kg/m²
|
1500 lbs
680 kg |
375 lbs
170 kg |
Min 2.5 |
600 lbs
272 kg |
600 lbs
272 kg |
150 lbs
68 kg |
| Related Applications >> Data Centers : Renovations |
Note: Concentrated, Ultimate,
& Impact Loads are applied on a one square inch area point load. Results
above indicate weakest port of panel. Other strengths available-consult
factory. For further information and product specifications, call us at
(949) 837-9194.
* = Panel shall be capable of withstanding withour failure a minimum
safety factor of 2.5 applied to the panel's concentration load rating. |
|
|